506467-01 Issue 1008 Page 1
The equipment covered in this manual is to be installed by trained and experienced service
and installation technicians. Improper installation, modification, service, or use can cause
electrical shock, fire, explosion, or other conditions which may cause personal injury, death,
or property damage. Use appropriate safety gear including safety glasses and gloves when
installing this equipment.
WARNING
Save these instructions for future reference
INSTALLATION AND MAINTENANCE INSTRUCTIONS
4AC16LT SERIES
Split System Air Conditioner
TABLE OF CONTENTS
INSTALLATION ....................................................2
START-UP .......................................................... 12
OPERATION ...................................................... 16
MAINTENANCE ................................................. 20
CONNECTION DIAGRAM .................................. 22
Manufactured By
Allied Air Enterprises, Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*506467-01*
Sharp metal edges can cause injury. When installing
the unit, use care to avoid sharp edges.
WARNING
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualified service personnel should install or service this
equipment. Installation and service performed by
unqualified persons can result in property damage,
personal injury, or death.
WARNING
Risk of electrical shock. Disconnect all remote power
supplies before installing or servicing any portion of the
system. Failure to disconnect power supplies can result
in property damage, personal injury, or death.
WARNING
Seitenansicht 0
1 2 3 4 5 6 ... 21 22

Inhaltsverzeichnis

Seite 1 - 4AC16LT SERIES

506467-01 Issue 1008 Page 1 The equipment covered in this manual is to be installed by trained and experienced serviceand installation techni

Seite 2 - INSTALLATION

506467-01 Issue 1008

Seite 4

506467-01 Issue 1008

Seite 5 - Figure 5

506467-01 Issue 1008

Seite 6 - Figure 7

506467-01 Issue 1008 Page 14 6. Compare the approach value with those shown in Table7. If the values do not agree with those provided in

Seite 7

506467-01 Issue 1008 Page 15Table 8Normal Operating PressuresL = Liquid S = SuctionValues provided above are typical pressures. Indoor unit match

Seite 8 - Page 8

506467-01 Issue 1008

Seite 9

506467-01 Issue 1008

Seite 10

506467-01 Issue 1008

Seite 11

506467-01 Issue 1008

Seite 12 - .ni8/3.tf5rep.zo3

506467-01 Issue 1008INSTALLATIONInspection of ShipmentUpon receipt of equipment, carefully inspect it for possibleshipping damage. If damage is found

Seite 14

506467-01 Issue 1008

Seite 16 - OPERATION

506467-01 Issue 1008Electrical WiringAll field wiring must be done in accordance with the NationalElectrical Code (NEC) recommendations, CanadianElec

Seite 17

506467-01 Issue 1008PlacementBe aware that some localities are adopting sound ordinancesbased on how noisy the unit is at the neighbor’s home, notat

Seite 18

506467-01 Issue 1008

Seite 19

506467-01 Issue 1008

Seite 20

506467-01 Issue 1008

Seite 21

506467-01 Issue 1008(It may be necessary to bypass the low pressure switchesto ensure complete refrigerant evacuation.)When the low side system press

Seite 22 - 24 VOLT FACTORY INSTALLED

506467-01 Issue 1008Manifold Gauge SetManifold guage sets used with systems charged with R410Arefrigerant must be capable of handling the higher syst